Category: Design
Prepared by Eng. Ahmed Fathy, Projects Manager ·
Definition
Uniformity commonly uses minimum divided by average illuminance, but state the definition. Use one measurement grid and plane; uniformity does not replace glare assessment.
Why it matters on a project
A good average can conceal dark spots in reading or circulation areas.
Measurement and pricing
Check grid, area boundaries, point distribution, average, minimum and the project's criterion.
Worked example
An example grid gives average 300 lux and minimum 180 lux: minimum-to-average uniformity is 180 ÷ 300 = 0.6. Compare with the space's specified criterion; this is not a universal acceptance limit.
Common mistake
Confusing minimum-to-average with minimum-to-maximum or omitting low readings.
Frequently asked questions
Will increasing the average solve it?
Unevenness may remain; review layout and distribution.
Is measurement always at floor level?
Choose the plane required for the surface and task.
Related terms
- Illuminance in luxIncident luminous flux per unit area.
- Reflected ceiling planA drawing of suspended ceilings, their levels, lights and diffusers.
- Testing and commissioningA documented process verifying system readiness and operating performance.