Saudi Arabia · Egypt Client portal +966 59 700 9855 info@arabcreators.co
Arab Creators Engineering Consultancy

Duct air velocity

سرعة الهواء داخل الدكت

Average air speed across the duct's clear internal area.

Category: Design

Prepared by Eng. Ahmed Fathy, Projects Manager ·

Definition

Duct velocity relates airflow to free internal section area. It affects pressure loss and noise, so the designer selects the section for system performance and available space.

Why it matters on a project

Reducing a duct to pass beneath a beam can raise velocity and pressure loss and affect delivered airflow.

Measurement and pricing

Divide flow rate by clear area, converting units and allowing for internal lining, then compare with the design.

Worked example

Airflow of 600 L/s is 600 ÷ 1000 = 0.60 m³/s. With clear section 0.50 × 0.30 = 0.15 m², velocity is 0.60 ÷ 0.15 = 4 m/s. Section adequacy still requires pressure-loss and noise checks.

Common mistake

Using outside dimensions for a lined duct or mixing litres per second with cubic metres per second.

Frequently asked questions

Is one velocity suitable for every duct?

No. Consider system type, duct location, noise and pressure loss.

What does internal lining change?

It reduces free area unless the stated dimensions are already clear of the lining.

Related terms

Read next

Does your project need architectural design and construction drawings? Send the drawings or a short description and we reply within one working day.

Service detailsRequest a quote