Category: Design
Prepared by Eng. Ahmed Fathy, Projects Manager ·
Definition
Voltage drop results from conductor impedance carrying current and depends on length, section, temperature, power factor and circuit arrangement. Check it alongside current capacity and protection, not instead of them.
Why it matters on a project
Nearby equipment can work correctly while a distant load is affected if the actual route length was ignored.
Measurement and pricing
Calculate using cable data, route length, design current and the appropriate circuit method, or measure under known load. Compare with the applicable project criterion.
Worked example
Source voltage is 230 V and load voltage is 224 V under the same condition: drop is 230 − 224 = 6 V, or 6 ÷ 230 × 100 = 2.61% approximately. This is an arithmetic example, not acceptance or cable selection.
Common mistake
Applying a single-phase formula to a three-phase circuit or doubling the route length twice.
Frequently asked questions
Does a voltage-drop check alone select the cable?
No. Also check ampacity, protection, fault conditions and installation factors.
Does a no-load reading establish operating drop?
No. State the load condition under which readings are taken.
Related terms
- Electrical load scheduleA table summing each board's loads to size breakers, cables and the meter.
- MEP drawingsElectrical, plumbing, HVAC and fire drawings.
- Inspection request (IR)A formal request from the contractor to the consultant to inspect work before the next stage.