Category: Design
Prepared by Eng. Ahmed Fathy, Projects Manager ·
Definition
Required head includes elevation and pressure differences and flow-dependent losses, accounting for inlet pressure and velocity differences where relevant. Express all terms consistently as liquid head.
Why it matters on a project
Building height alone does not provide required pressure at the remote fixture.
Measurement and pricing
Define reference points, design flow, pipe sizes, fittings and source and outlet pressures.
Worked example
From an open tank surface to a fixture, neglecting velocity-head difference: elevation is 12 m, required residual head 18 m and losses 7 m, giving 12 + 18 + 7 = 37 m. Initial gauge pressure at the tank surface is zero.
Common mistake
Counting elevation twice or ignoring available inlet pressure.
Frequently asked questions
Are pipe losses constant?
They depend on flow, diameter, roughness and fittings.
Is inlet pressure simply added?
Use the energy balance with correct signs; available source pressure usually reduces required pump head.
Related terms
- Booster pump duty pointA specified flow and head for pump selection and operation.
- MEP drawingsElectrical, plumbing, HVAC and fire drawings.
- Pipe pressure testTesting a pipe system at a pressure and duration defined by an approved procedure.
Read next
Does your project need architectural design and construction drawings? Send the drawings or a short description and we reply within one working day.
Service detailsRequest a quote