Definition
Protective conductor continuity checks the metallic path between the earthing point and parts requiring bonding. It differs from earth electrode resistance and residual-current device testing.
Why it matters on a project
A visible conductor can still be broken or loosely connected, impairing protection.
Measurement and pricing
A competent person tests it with suitable equipment after isolation and proving dead, allowing for test-lead resistance and assessing readings under the design and procedure.
Worked example
An illustrative 0.18 ohm reading includes 0.05 ohm test-lead resistance: corrected reading is 0.18 − 0.05 = 0.13 ohm. A competent tester assesses it against the path and procedure; the example supplies no acceptance limit.
Common mistake
Treating an electrode resistance test as proof that every circuit and item has a continuous protective conductor.
Frequently asked questions
Is this soil resistance testing?
No. It checks the protective conductor path in the installation.
Is isolation required?
The competent tester follows the approved isolation, proving-dead and test procedure.